EX Intrinsically Safe Evacuation Button CP 135The flameproof CP135 evacuation button is ATEX / IECEx certified for use in potentially explosive
atmospheres. It can be used in conjunction with a fire alarm system will activate alarms to alert personnel
to potential dangers, help signal the need for immediate action in emergency situations and more.
Also known as explosion proof fire alarm call point, manual call point (MCP) or “Break Glass” call point.
ATEX / IECEx Certification: ATEX Zone 1 and Zone 2 Certified for group IIB +H2 gas / vapour applications and Zone 21 and Zone 22 compliant for dust / powder applications. SIL2 compliant as IEC 61508 & IEC 61511.
Application: Oil and gas, chemical, petrochemical, pharmaceutical, marine and offshore applications
Key features: Robust and highly reliable, this Ex manual call point (MCP) / Break Glass call point is designed for corrosive environments and hazardous areas. The housing is moulded in Glass-Reinforced Polyester (GRP), protected by an UV resistant paint. These ATEX / IECEx compliant manual call points / “Break Glass” call points are compatible with PLC, ESD and DCS systems. There is a built in test function.
Options: Visualisation functions, line detection, glass protection and hammer are optional. A range of accessories is available to customise this ATEX / IECEx manual call point / “Break Glass” call point.
These include pipe mounting brackets, sunshades, tag and duty labels and other accessories.
ATEX EX Intrinsically Safe Evacuation Button CP 135Colour range:
• red: RAL3001/3028 • green: RAL6032
• blue: RAL5005 • yellow with black stripes: RAL1018 + RAL1005
• grey: RAL7038 • black: RAL9005
• orange: RAL2010 • yellow: RAL1018
Classification II 2 GD Ex d IIB + H2 T6 Gb; Ex tb IIIC T85°C ATEX area zone Gas zone: 1&2,

Dust zone: 21&22
ATEX certificate Nemko 13 ATEX 1568X, IECEX NEM 13.0038X
Standards EN/IEC 60079-0, EN/IEC 60079-1,
EN/IEC 60079-31/ EN 54-11

Main characteristics

  • Enclosure material Glass-Reinforced Polyester (GRP)
  • Rated impulse withstand voltage 1 kV according to IEC 61000-4-5
  • Contact type 1× C/O or 2× C/O (1)
  • Rating (resistive load) 125/250VAC (50/60Hz) =11A; 30VDC= 6A;
  • 125VDC
  • = 0,3A; 250VDC
  • = 0,6A
  • Minimum voltage and current 5VDC 10mA
  • Shorts circuit protection 10 A gG
  • Cables entry 2× M20, 1× M25 + 1× M20,
  • 1× 1/2’’ NPT + 1× M20,
  • 1× 3/4’’ NPT + 1× M20
  • Terminals From 22 to 14 AWG: 0.50-2.5 mm²
  • Line resistor (optional) 470 Ohms • 1 Watt
  • Signalling LED (optional) Green U =24VDC I= 10 mA;
  • Red U=24VDC I = 20mA
  • Ambient temperature T6 = -40~55°C, T5 = -40~60°C, T4 = -40~70°C
  • Ambient humidity (without runoff) up to 95%
  • Enclosure protection level IP67
  • Dimensions (W×H×D) 135 × 135 × 84 mm
  • Net weight 2.0 Kg