EX EARTHING CLAMP FOR GROUNDING ROADTANKER
ATEX CERTIFIED EARTHING CLAMP To unload ROADTANKER in ATEX Zone 1/21

The Logic ECS-RF system can be effectively used to earth tanker trucks in ATEX Zone 1/21. The system makes it possible to dissipate any electrostatic charges generated when handling flammable liquids, by continuously verifying via the SIL2 electronics (ECS-RF version) that the resistance to earth is always <10Ω.
With their many variants and accessories, ECS-RF series devices can be adapted to any application.
Connection clamps:
IS1L in die-cast aluminium for drums and large IBCs CLP-MINI in stainless steel for small drums and small metal containers.
TECHNICAL SPECIFICATIONS
- Control unit installation area ECS-RF-DIN: electronics in Safe Area
ECS-RF: ATEX Zone 1/21 - Temperature range Control unit in safe area: -20°C ≤ Tamb ≤ +70°C
- Control unit ATEX Zone 1/21: -20°C ≤ Tamb ≤ +40 °C
- Standard cable: 5 m 6-wire coiled cable for Ex i applications
Optional connections 10 m 6-wire coiled cable for Ex i applications
CR-20 reel in AISI 304 with two-wire cable L=20 m - Power supply: AC version (ECS-RF-DIN): 230 Vac, Um=253 Vrms
DC version (ECS-RF-DIN-DC): 10÷30 Vdc, Um=30 Vdc / 253 Vdc
Control unit dimensions (L x H x D): Control unit for safe area (ECS-RF-DIN): 162 x 90 x 65 mm - Control unit for ATEX Zone 1/21 (ECS-RF): 195 x 195 x 148 mm
- Control unit installation area ECS-RF-DIN: electronics in Safe Area ECS-RF: ATEX Zone 1/21
- Temperature range Control unit in safe area: -20 °C ≤ Tamb ≤ +70 °C
IS1L CLAMP SPECIFICATIONS
- Clamp composition: Die-cast aluminium with plastic handle
- Status display: Via green and red LED on the clamp
- Clamp connection: area ATEX Zone 0/20
- Operating temperature: -20°C ≤ Tamb ≤ +55 °C
- Dimensions (L x H x D): 250 x 110 x 95 mm